Värmepumpar Industri
Technological innovation
The MWK40 earned the quality seal in five of a total of seven categories at the Plus X awards which is one of the biggest technology innovation prizes in the world. With the seals awarded in Innovation, High Quality, Ease of Use, Functionality and Ecology we know that whatever your needs are we can meet and surpass them. Read more: www.plusxaward.de/en
Advantages of the mobile air-to-air heat pumps MWK40, MW40 and MW80
- Environmentally friendly
- Economical
- Fossil-free
- Mobile
- Compact
- (Festival) tents
- (Large) events
- (Large) construction sites
- Warehouses & Production halls
- Agriculture
- Additional heating
- Temporary heating in case of failure of stationary heating systems
- Temporary cooling for all uses above (MWK40 only)
Application Standard ambient temperatures
- Standard use is for outdoor temperatures of -20 ° C - + 25 ° C
- Summer and transition time permanently switching depending on the outside temperature
Option Application High ambient temperatures
- MWK40 offers combined heating and cooling for outdoor temperatures of -10 ° C - + 40 ° C
Compact design
- No protruding components
- Intake and exhaust nozzles can be retracted in the housing
- Fork sleeves for safe loading with the forklift and additional lifting eye
- Safe stackable
Economics
Increased mobility
Serviceability
All components are easily accessible and easily serviceable thanks to removable side panels. Kropp heat pumps are delivered with a router installed by default, providing the customer with a Wi-Fi connection and control on-site.
The heat pumps come with the option of remote maintenance, diagnostic reports and operating status as well as remote software updates. Additionally the heat pumps can be equipped with remote access to operating parameters and retrieval of historical data. The
Model |
No. |
MWK40 300686 |
MW40 301531 |
MW80 301532 |
Function |
Heating and cooling |
Heating |
Heating |
|
Application ambient temperature |
°C |
–10 to +40 |
–20 to +25 |
–20 to +25 |
Heat capacity (A7/L35) |
kW |
42,9 |
42,4 |
100,4 |
Cooling capacity (A30/L12) |
kW |
33,5 |
– |
– |
COPh (A-7/L35) without utilizable medium |
2,24 |
2,30 |
2,34 |
|
COPh (A2/L35) without utilizable medium |
2,88 |
2,76 |
2,77 |
|
COPh (A7/L35) without utilizable medium |
3,31 |
3,07 |
3,06 |
|
SCOPh without utilizable medium |
2,88 |
2,72 |
2,73 |
|
COPh (A-7/L35) with utilizable medium |
1,95 |
1,96 |
2,04 |
|
COPh (A2/L35) with utilizable medium |
2,50 |
2,42 |
2,46 |
|
COPh (A7/L35) with utilizable medium |
2,88 |
2,69 |
2,71 |
|
SCOPh with utilizable medium |
2,45 |
2,34 |
2,38 |
|
Volume |
m /h |
8.000 |
8.000 |
16.000 |
External pressure |
Pa |
200 |
200 |
250 |
Electrical connection |
V/ Ph/Hz |
400/3/50 |
400/3/50 |
400/3/50 |
Connector plug |
32 A CEE |
32 A CEE |
63A CEE |
|
Max. nominal current |
A |
31 |
31 |
62 |
Connection Ø air current |
mm |
525 |
525 |
525 |
Length |
mm |
2.400 |
2.400 |
3.000 |
Width |
mm |
1.200 |
1.200 |
2.300 |
Height |
mm |
2.200 |
2.200 |
2.350 |
Weight |
kg |
1.000 |
1.100 |
2.700 |
Sound pressure level |
dB(A) |
66 |
66 |
68 |
Refrigerant |
R410A |
R454C |
R454C |
|
Compressor |
Scroll |
reciprocating compressor |
reciprocating compressor |
|
Condensate quantity max. |
liter/h |
10 |
10 |
20 |
Nozzle condensate drain (external) |
Inch |
1 1/4 |
1 1/4 |